Articles database
 
 
Web AnyArticles.com
Browse by Category:
 
  Subcategories
College University College University (297)
Psychology Psychology (151)
Science Science (457)


  Categories :
 
  Arts and Entertainment
  Automotive
  Business
  Communications
  Computers and Technology
  Finance
  Food and Drink
  Health and Fitness
  Home and Family
  Home Based Business
  Internet and Businesses Online
  Kids and Teens
  Legal
  News and Society
  Recreation and Sports
  Reference and Education
  Self Improvement
  Shopping and Product Reviews
  Travel and Leisure
  Womens Interests
  Writing and Speaking
  Random Category
  Innovation
  Hardware
  Funny stuff
Reference and Education article : How Do PID Controllers Work: Application & Theory
 

Reference and Education > How Do PID Controllers Work: Application & Theory

0 Reviews [ add review ], Article rating : 0.00, 0 votes. Author : Joe Crew

What is a PID controller?

A PID (Proportional Integral Derivative) controller is a common instrument used in industrial control applications. A PID controller can be used for regulation of speed, temperature, flow, pressure and other process variables. Field mounted PID controllers can be placed close to the sensor or the control regulation device and be monitored centrally using a SCADA system.

Example: Temperature Control using a Digital PID controller

A typical PID temperature controller application could be to continuously vary a regulator which can alter a process temperature. This may be a pulsed switching device for electrical heaters or by opening and closing a gas valve. A heat only PID temperature controller uses a reverse output action, i.e. more power is applied when the temperature is below the setpoint and less power when above. PID control for injection and extrusion applications often employ additional cooling control outputs and usually require multiple controllers.

A PID controller (sometimes called a three term controller) reads the sensor signal, normally from a thermocouple or RTD, and converts the measurement to engineering units e.g. Degrees C. It then subtracts the measurement from a desired setpoint to determine an error.

The error is acted upon by the three (P, I & D) terms simultaneously:

PID Controller Theory

The following section examines PID controller theory and provides further explanation of the question `how do PID controllers work'.

Proportional (Gain)

The error is multiplied by a negative (for reverse action) proportional constant P, and added to the current output. P represents the band over which a controller's output is proportional to the error of the system. E.g. for a heater, a controller with a proportional band of 10 deg C and a setpoint of 100 deg C would have an output of 100% up to 90 deg C, 50% at 95 Deg C and 10% at 99 deg C. If the temperature overshoots the setpoint value, the heating power would be cut back further. Proportional only control can provide a stable process temperature but there will always be an error between the required setpoint and the actual process temperature.

Integral (Reset)

The error is integrated (averaged) over a period of time, and then multiplied by a constant I, and added to the current control output. I represents the steady state error of the system and will remove setpoint / measured value errors. For many applications Proportional + Integral control will be satisfactory with good stability and at the desired setpoint.

Derivative (Rate)

The rate of change of the error is calculated with respect to time, multiplied by another constant D, and added to the output. The derivative term is used to determine a controller's response to a change or disturbance of the process temperature (e.g. opening an oven door). The larger the derivative term, the more rapidly the controller will respond to changes in the process value.

Tuning of PID Controller Terms

The P, I and D terms need to be "tuned" to suit the dynamics of the process being controlled. Any of the terms described above can cause the process to be unstable, or very slow to control, if not correctly set. These days temperature control using digital PID controllers have automatic auto-tune functions. During the auto-tune period the PID controller controls the power to the process and measures the rate of change, overshoot and response time of the plant. This is often based on the Zeigler-Nichols method of calculating controller term values. Once the auto-tune period is completed the P, I & D values are stored and used by the PID controller.

Joe Crew is the Product Manager at Data Track Process Instruments Ltd. Data Track manufactures digital panel meters, large number displays, PID controllers, signal conditioners and remote data acquisition systems for the process and control industry. Data Track can also supply HMI touchscreen operator panels and SCADA software. The Tracker 300 series of PID Controllers are fully configurable by PC software and feature universal input, single loop integrity, autotune PID, heat / cool control actions and condition monitoring features.


0 Reviews [ add review ], Article rating : 0.00, 0 votes. Author : Joe Crew
Rate this story : and read/post review(s)


Article reviews



Post your review
[ Note : no HTML/URLs - will removed automatically ]
Your name
Your comments


More articles from Reference and Education

Add article | Manage Articles | Top Rated articles | Most Reviewed articles | Contact us | Links